APS Design in New Construction

Draft and Proposed PROWAG

Revised Draft Public Rights-of-Way Accessibility Guidelines (Draft PROWAG) were released on November 23, 2005. While Draft PROWAG has not been published as a final rule, it can be considered as the best guidance available at this time (Isler memo, 2006). Proposed Accessibility Guidelines for Pedestrian Facilities in the Public Right-of-Way were published July 26, 2011 (Proposed PROWAG) and incorporate the 2009 MUTCD by reference.

APS Characteristics

The Proposed PROWAG requires APS to meet MUTCD specifications in Section 4E.08 through Section 4E.13 in new construction and reconstruction where pedestrian signals are installed:

Proposed PROWAG also requires APS to meet requirements for Operable Parts found in PROWAG section R409.

Location in new construction

Figure 6-7. APS installation in new construction

Figure 6-7. APS installation in new construction

The Proposed PROWAG section on Operable Parts requires the pushbutton to be accessible by requiring :

MUTCD recommended locations

MUTCD 2009 has provided much more specific recommendations for the location of all pushbuttons (pedestrian detectors) which addresses the proposed PROWAG requirements above. Guidance in Paragraph 4 of the MUTCD Section 4E.08 states

04 If pedestrian pushbuttons are used, they should be capable of easy activation and conveniently located near each end of the crosswalks. Except as provided in Paragraphs 5 and 6, pedestrian pushbuttons should be located to meet all of the following criteria (see Figure 4E-3):

Paragraphs 5 and 6 are exceptions that allow for the surface to be as level as possible and for the pushbutton to be up to 10 feet from the curb if necessary.

Paragraph 7 of 4E.08 recommends that two pushbuttons on the same corner should be separated by at least 10 feet. Paragraph 8 allows pushbuttons to be closer, or on the same pole, “where there are physical constraints on a particular corner that make it impractical to provide the 10-foot separation.”

APS locations

Figure 6-8. Ideal placement for pushbutton-integrated APS

Figure 6-8. Ideal placement for pushbutton-integrated APS

APS locations

Figure 6-9. Acceptable placement for pushbutton-integrated APS

Figure 6-9. Acceptable placement for pushbutton-integrated APS

Location details

Figure 6-10. The APS should be located on the intersection side of the pole, as shown in this photo

Figure 6-10. The APS should be located on the intersection side of the pole, as shown in this photo

Figure 6-11. The MUTCD states that the APS should be within 5 feet of the crosswalk line

Figure 6-11. The MUTCD states that the APS should be within 5 feet of the crosswalk line

Figure 6-12. The APS should be within 6 feet of the curb, with an exception that allows APS to be placed up to 10 feet from the curb, if necessary

Figure 6-12. The APS should be within 6 feet of the curb, with an exception that allows APS to be placed up to 10 feet from the curb, if necessary

Installation Example

Figure 6-13. APS installed in this reconstruction location are in accordance with MUTCD and Proposed PROWAG in that they are beside a level landing and separated from each other by at least 10 feet (3 m). Both APS are located on the intersection side of their poles.

Figure 6-13. APS installed in this reconstruction location are in accordance with MUTCD and Proposed PROWAG in that they are beside a level landing and separated from each other by at least 10 feet (3 m). Both APS are located on the intersection side of their poles.

[ back to top ]